Masterys BC+ Flex

A system that fits every space
Three-phase UPS from 10 to 40 kVA

The solution for

• SME IT networking / computer rooms
• Building automation
• Payment systems
• Public sector
• Security control

Advantages

A flexible and cost-effective solution

• The Flex model eliminates space and installation restrictions with the «3-in-1» solution.
• Equipped with an output and manual bypass breaker in standard mode.
• Mimic panel can be rotated to enable the information displayed to be read easily.
• High recharging current option for very long back-up time.

Fast and easy installation

• Easy to configure for retrofit in existing installations.
• Free eRULER online sizing tool to get dimensions and electrical information in advance before installation.
• Quickly get online product documentation by simply inputting the Serial Number

User and environmentally friendly

• 25+ languages available in the mimic panel.
• Ergonomics designed to simplify usage.
• Anticipates eco-regulations and is RoHS compliant.

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Standard electrical features

• Built-in backfeed protection.
• Protection against atmospheric phenomena (NTP) for telephone/ADSL modems.
• RJ11 connection for Emergency Power Off (EPO).
• Connection for battery extension modules.

Electrical options

• Battery extension modules.

Standard communication features

• LOCAL VIEW: ideal UPS monitoring andshutdown point-to-point solution for Windows®, Linux and Mac OS X® operating systems.
• HID: UPS management based on Windows® and Mac OS X® embedded service – USB interface.
• MODBUS RTU.

Communication options

• RT-VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.

Sn [kVA]1015203040
Pn [kW]913.5182736
Input / output 3/1
Input / output 3/3
Parallel configurationup to 6 units
Input
Rated voltage

3ph + N: 400 V (can be configured 380/415 V)

Voltage tolerance

240 V to 480 V

Rated frequency50/60 Hz ± 10%
Output
Power factor0.9 (according to IEC/EN 62040-3)
Rated voltage
1ph + N: 230 V (can be configured 220/240 V)
3ph + N: 400 V (can be configured 380/415 V)
Rated frequency50/60 Hz
Efficiency (TÜV SÜD verified)
Double conversion VFI modeup to 95%
Eco modeup to 99%
Battery
TechnologiesVRLA, NiCd
Battery typenormal life
ConfigurationExternal batteries
Environment
Operating ambient temperatureup to +40 °C (2)
UPS cabinet 
Dimensions W x D x H442 x 830 x 305 mm
Weight79 kg max(1)
Display3.5”
Degree of protectionIP20 (IP21 on demand)
Coloursmetallised grey E150HVR
Standards
SafetyIEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
EMCIEC/EN 62040-2, AS 62040.2
PerformanceIEC/EN 62040-3, AS 62040.3
Environmentalfull compliance with the RoHS EU directive
Product declarationCE, RCM (E2376)

(1) According to the model.
(2) Conditions apply.

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings

Commercial (Hotel, shopping centre, stadium, cinema, TV station, etc.), Government, Residential.