Three/three phase UPS from 160 to 200 kVA

The EMergency CPSS range has been designed to answer your needs in terms of power supply for your safety system.

All our EMergency products are compliant with standard EN 50171.

The EMergency CPSS products are intended to ensure energy supply to emergency escape lighting in the event of main supply failure. Depending on the local legislation, it may be suitable for energizing other essential safety equipment, such as:
• electric circuits of automatic fire extinguishing installations;
• paging systems and signaling safety installations;
• smoke extraction equipment;
• carbon monoxide warning systems;
• special safety installations related to specific buildings, e.g. high-risk areas.

The wide range fits all standard needs. For the non-standard request, our expert team will be at your service to adapt the products to your needs.
 

The solution for

• Airports
• Railways and bus stations
• Schools and universities
• Hospitals
• Shopping centers
• Cinemas and theatres
• Museums
• Public buildings
• Office buildings
• Hotels

Standard features

• IP20 metal enclosure compliant with EN60598-1.
• Battery charging: 80% in 12 hours.
• Battery protection against the damage due to a polarity inversion.
• Battery protection against deep discharge.
• Long life battery with 10 year-life expectancy.
• Designed to withstand 120% of the nominal charge during the entire back-up period.
• Specific dry contacts & monitoring for EMergency system

Options

• Transformer embedded in the UPS enclosure (contact us for further information)
• Connection to downstream IT earthing system
• Eco mode to reach up to 98% of efficiency
• Other types of battery available

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Sn [VA]160200
Pn [W]144180
Pn according to EN 50171 [kW]120150
Input / output(3/3)(3/3)
Input
Rated voltage400 V 3ph
Voltage tolerance240 V to 480 V(1)
Rated frequency50 – 60 Hz
Frequency tolerance± 10 %
Power factor / THDI> 0.99 / < 3 %
Output
Rated voltage400 V
Voltage tolerancestatic load ± 1 % dynamic load in accordance with VFI-SS-111
Rated frequency50 – 60 Hz
Frequency tolerance± 2 % (configurable from 1 % to 8 %)
Overload UPS designed110 % for 10 min, 135 % for 1 min
Crest factor3:1
UPS Cabinet
Dimensions W x D x H 700x800x1930 mm
Maximum weight with embedded battery
Maximum weight without battery480 kg500 kg
Protection degreeIP 20 (EN 50171)
Acoustic level 1m (ISO 3756)< 68 dBA
Battery
TypeVRLA with 10 years-life expectancy
Standard back-up time at the end of battery life60/90/120 min (1)
Charging capabillity80 % of the back-up time in 12h
External battery
Standards
CPSSEN 50171
SafetyIEC/EN 62040-1
EMCIEC/EN 62040-2
PerformanceIEC/EN 62040-3
Product declarationCE

(1) Condition apply

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings