Delphys MP Elite+

Resilient transformer-based power protection. Three/three phase UPS from 80 to 200 kVA

The solution for

• Industry
• Processes
• Infrastructure
• Healthcare
• Service sector
• Telecommunications

Advantages

High quality power supply

• Permanent operation in VFI mode (online double conversion).
• Output voltage precision under all load conditions.
• High overload capacity to withstand abnormal load conditions.
• A very high short-circuit current capacity which facilitates the selection of protective devices for selectivity in the downstream distribution.
• An isolation transformer installed on the inverter output to ensure complete galvanic isolation between DC circuit and load output. This insulation also provides a separation between the two inputs when they are supplied by different sources.
• Sinusoidal ThdU output voltage < 2 % with linear loads and < 4 % with non-linear loads.

High availability

• Field-proven technology.
• Fault-tolerant architecture with redundancy of basic functions, such as the ventilation system.
• Easy maintainability reduces MTTR thanks to pull-out sub-assemblies and front access all components.
• Accurate diagnostics guarantee power supply to the load.
• Cascade failure prevention for parallel systems.
• Mechanical & electrical robustness for industrial environments.
• Soft start capability (ramp up) of the IGBT inverter allows a good operation even with a genset.
• Specifically designed to be adapted to different industrial environment: high IP protection options, high peak current capability, long back up time…

Cost-effective equipment

• The “clean” IGBT rectifier allows:
– a high efficiency,
– a high and constant input power factor,
– a low THDi.
These characteristics help to limit the dimensions of upstream network infrastructure.
• Possibility to create new neutral system without additional losses (extra transformer required on by-pass line only).
• High short-circuit capability simplifies downstream protective devices.
• High power density: its small footprint saves space on your premises.
• Mains connection of the rectifier requires only 3 cables (no neutral).
• Battery connection to UPS requires only 2 cables.

User-friendly operation

• A control panel with graphic display for more ergonomic operation.
• An array of “com-slot” plug-in communication interfaces, for upgrading your operating requirements evolution.

Simplified maintenance

• An advanced diagnostic system.
• A remote access device connected to the remote maintenance centre.
• Easy access to subassemblies and components, facilitating tests and reducing maintenance time (MTTR).

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Parallel systems

• Distributed or centralized bypass for parallel architecture up to 6 units.
• Redundant systems (“1+1” and “n+1”).
• “2n” architecture with Static Transfer Systems.

Standard electrical features

• Slots for 3 communication cards.
• Backfeed protection: detection circuit.
• Standard interface:
– 3 inputs (emergency stop, generating set, battery protection),
– 4 outputs (general alarm, back-up, bypass, preventative maintenance needs).

Electrical options

• EBS (Expert Battery System)(2).
• ACS synchronisation system for 2n architecture.
• Redundant electronic power supplies.
• Hot plug option (increase the power keeping the load supplied in double conversion).
• Long back up time rectifier.

Mechanical options

• Reinforced IP protection degree.
• Dust filters.
• Fan redundancy with failure detection.
• Top entry connection.
• Reinforced IP protection up to IP52.

Communication options 

• GTS (Graphic Touch Screen).
• ADC interface (configurable voltage-free contacts).
• MODBUS RTU.
• MODBUS TCP.
• PROFIBUS / PROFINET.
• BACnet/IP interface.
• NET VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.
• 3 extra slots for communication cards.

Remote monitoring service

• LINK-UPS, remote monitoring service that connects your UPS to your Critical Power specialist 24/7

Sn [kVA]80100120160200
Pn [kW]7290108144180
Input / output3/3
Parallel configurationup to 6 units (distributed or centralised bypass)
Input
Rated voltage

380 V – 400 V – 415 V(1)

Voltage tolerance

342 to 460 V(2)

Rated frequency50/60 Hz
Frequency tolerance45 to 65 Hz
Power factor / THDI0.99 constant / 2.5 % without filter
Output
Rated voltage380 V – 400 V – 415 V (configurable)(1)
Voltage tolerance< 1 % (static load), ± 2 % in 5 ms (dynamic load conditions from 0 to 100 %)
Rated frequency50/60 Hz
Frequency tolerance± 0.2%
Total output voltage distortion – linear loadThdU <2%
Total output voltage distortion – non-linear loadThdU <4%
Short-circuit current on inverter (100ms)Up to 3.5 In
Overload150 % for 1 minute, 125 % for 10 minutes(2)
Crest factor 3:1
Bypass
Rated voltage380 V – 400 V – 415 V
Voltage tolerance± 10% (selectable)
Rated frequency50/60 Hz
Frequency tolerance± 2% (configurable for GenSet compatibility)
Short-circuit current on by-pass (20ms)Up to 24 In
Efficiency
Online mode93,5%
Eco Mode98%
Environment
Operating ambient temperaturefrom 0 °C up to +40 °C(2) (from 15 °C to 25 °C for maximum battery life)
Relative humidity0% – 95% without condensation
Maximum altitude1000 m without derating (max. 3000 m)
Acoustic level at 1 m
(ISO 3746)
65 dBA67 dBA
UPS cabinet 
Dimensions W x D x H1000 x 800 x 1930 mm
Weight740 kg860 kg1020 kg
Degree of protectionIP20 (other IP as option)
ColoursRAL 9006
Standards
SafetyIEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
EMCIEC/EN 62040-2, AS 62040.2
Product declarationCE, RCM (E2376)

(1) Others on demand.
(2) Conditions apply.

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings

Commercial (Hotel, shopping centre, stadium, cinema, TV station, etc.), Government, Residential.