Sharys IP Enclosure

Rugged, reliable DC power solution
from 15 to 100 A

The SHARYS IP series have been designed with the objective of reliable DC supply.

Advantages

A modular and flexible range

• Expandable according to future requirements by adding additional rectifier modules.

Reliability and robustness

• Robust steel frame.
• PCB tropicalisation as standard.
• Microprocessor control.
• Intelligent rectifier cooling.
• Battery safe thanks to the end of discharge protection (option).
• Limited thermal stress and longer life of the components.

Total Costs of Ownership (TCO)

• High efficiency up to 93%: low energy consumption, low heat dissipation.
• Sinusoidal current absorption with power factor close to one: low conductor heat dissipation and no plant oversize.
• Easy to install.
• Reduced maintenance costs.
• Process continuity with hot-swap capabilities (replacement of modules without any power interruption).

Easy, user-friendly operation

• Front mimic panel with clear working status indication.
• Digital control and monitoring of the rectifier modules.
• Adapted to be used with different types of battery technologies.
• Wide choice of communication interfaces: Dry contact, MODBUS RTU, SNMP with NET VISION option.


(1) Contact us for power extension or customization need

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Standard electrical features

• Polarity insulated or grounded.
• Internal battery protection.
• Fitting for output DC distribution.
• Battery temperature sensor.
• PCB tropicalization.
• IP30 steel cabinet.
• Pallet truck friendly base.

Electrical options

• BLVD battery low voltage disconnector.
• Output distribution.
• Double AC power supply
• Double string battery protection.
• Emergency Power Off (EPO).
• Power Share.
• Coupling kit.
• Earth leakage control.
• Input surge suppressors.
• Battery cabinet.
• Enhanced protection degree.

Standard communication features

• Dry contact interface.

 

 ENCLOSURE EDENCLOSURE EX
Input
Rated voltage230 V 1ph + N400 V 2ph
Voltage tolerance± 20% @ 100% Pn up to a -50% @ 40% Pn
Frequencyfrom 47.5 to 63 Hz
Input transformerincluded in standard
Output
Output voltage (V)24481081202448108120
Rated current (A)100306010040100306010040
Maximum power (kW)2.41.42.94.84.34.82.41.42.94.84.34.8
Voltage regulation (V)(1)21-2942-5895-131105-14521-2942-5895-131105-145
Voltage ripple50 mVrms 100 mVpp
Efficiency
Typical> 90%
Environnement
Operating ambient temperature-5 ÷ 45 °C without derating, up to 55 °C with power derating
Relative humidity10% to 90%
CoolingForced with intelligent fan speed control
RECTIFIER CABINET
Dimensions W x D x H (2)600 x 535 x (894 to 1254) mm
Min-max weight (3)60 to 75 kg
Degree of protectionIP30
ColorRAL 7012
Standards
SafetyIEC/EN 61204-7
EMCEN 61204-3, EN 61000-6-4, EN 61000-6-2
PerformanceIEC/EN 61204
Resistance to vibrationsASTM D999
Resistance to fallsASTM D5276

(1) Output voltage variation depends on the recharging voltage and on the end of the discharging voltage settings (typically 1.13 Vn with mains present and battery charged, 0.90 Vn when batteries are completely discharged).
(2) Height depends on accessories and backup time.
(3) Without batteries.

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings