Statys Integrable Chassis

Redundant design for power availability and site maintainability
Static Transfer System from 200 to 1800 A

Advantages

STATYS provides

• High  reliability – internal redundant design. Flexibility and adaptability to various types of applications.
• Compact design: saves up to 40% of valuable space.
• Operational security and ease of use Remote data access in real time and from any location.
• Full support and service.

High availability

• Complete separation of both sources and the related distribution systems.
• Dual source redundancy supplies the load choosing the best source quality ensuring continuity
• No-break transfer of the loads.
• Distributed STS for load separation avoiding mutual disturbances.
• Full internal redundant design and failure management.
• Separation of main functions to prevent internal fault propagation.
• Neutral loss detection on both sources.

High flexibility

• Suitable for all types of:
– applications and power supply systems,
– electrical environment conditions,
– load to protect.
• Easy installation:
– for existing or new electrical plants,
– compact units,
– front access.
• Available with or without neutral connection and with or without neutral pole switching.

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Size (A)20030040060080010001250140016001800
Electrical specifications
Voltage208 – 220 / 380 – 415 / 440 V (±10%)
Number of phases3ph+N or 3ph (+ PE)
Frequency 50 Hz or 60 Hz (configurable ±5%)
Number of poles switching3 or 4-pole switching
Neutral systemCompatible with all earthing systems
Maintenance bypassInterlocked and secured
Overload150% for 2 minutes – 110% for 60 minutes
Efficiency99%
Admissible power factorNo restrictions
Environment
Operating ambient temperature0 – 40°C
Relative humidity95 %
Maximum altitude1000 m a.s.l. without derating
CoolingForced ventilation
Acoustic level at 1 m (ISO 3746)< 60 dBA
Mechanical specifications
Dimensions W x D x H (1)400 x 586 x 765 mm600 x 586 x 765 mm800 x 586 x 765 mm1000 x 950 x 1930 mm910 x 815 x 1955 mm
Weight70 kg105 kg130 kg495 kg750 kg
Degree of protectionIP20
Standards
Performance and safetyIEC 62310, IEC 60529, AS 62310, AS 60529
EMCC2 category (IEC 62310-2, AS 62310.2)
Protection classCB or PC class
Product declarationCE, RCM (E2376)

(1) Depth does not include handles (+40 mm).

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings

Commercial (Hotel, shopping centre, stadium, cinema, TV station, etc.), Government, Residential.