Modylys RM GP

Rack-mounted modular UPS system
Three/three phase UPS up to 4 x 25 kW

MODULYS RM GP is a 3-phase modular UPS system designed for 19” rack integration. 
Easy to integrate and install whilst simple to manage and maintain, it provides maximum availability and power protection in a compact design leaving free space for other rack-mounted devices.

Designed for 19” rack integration

Easy to integrate

• Specifically designed for integration in 19” standard rack cabinets.
• Adjustable rails and mounting accessories.
• Pre-cabled system for simplified connections.

No-risk integration

• Assured compatibility with any 19” standard rack cabinet.
• Pre-engineered and lab-tested parts assuring total system reliability.
• Automatic self-configuration power modules.

Easy to customise

• Complete set of pre-engineered and pretested parts to meet any customer need.

 

Easy to manage

• Full documentation package including schematics, integration instructions, technical sheets, etc.
• Factory-set configurations for easy model selection.
• Full set of pre-engineered options for easy product customisation.

Overall cost optimisation

• Compact sub-rack enclosure saving valuable cabinet rack space.
• 2 sub-rack enclosure models for optimum sizing.
• Best-in-class €/ kW ratio thanks to high power density and PF=1.
• Plug & Play and self-configuration power modules for easy and time saving system set up.
• Pre-engineered and lab-tested parts for easy and time saving customisation.

Simplified logistics

• Fewer standardised parts for easy ordering.
• Parts always in stock for fast procurement.
• Fewer parts covering a wide range of configurations, power, back-up time and options.

Designed to assure absolute business continuity

Total resilience

• Electronics-free (failure-free) sub-rack enclosure.
• Totally independent and self-sufficient modules.
• No centralised control for parallel and load sharing management.
• Totally segregated, fully sized and centralised auxiliary mains bypass and distributed inverter bypass.
• Configurable N+1 redundancy (power & battery).
• No single point of failure.
• Redundant parallel bus connection (ring configuration).

Optimum reliability

• Power module designed for superior robustness verified by an independent body (MTBF > 1,000,000 hr).
• Highly robust bypass (MTBF > 10,000,000 hr)
• Acid leak-proof modular battery box.

Maximum availability

• Fast recovery of lost redundancy thanks to minimum MTTR (Mean Time To Repair).
• No risk of downtime during power upgrading and maintenance.
• No risk of failure propagation.

Pay as you need

• Totally modular rack-mounting system for power scaling or for quickly adapting to business changes.
• No prior expenditure for unpredictable future extensions in power and back up time.
• No need to duplicate the system hardware to get redundancy.

Enhanced serviceability performance

• Fast and safe maintenance based on hot-swap parts (power modules, bypass, electronic boards, batteries).
• Safe and risk-free maintenance: only sealed box is replaced, no exposed live parts.
• Concurrent maintenance: no need to switch on static bypass or maintenance bypass.
• Battery can be hot-swapped without shutting down the connected equipment.

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Designed to assure absolute business continuity

 

Certifications and attestations

4pictos-Modulys-RM-GP.jpg

Technical data

 MODULYS RM GP
Model 9U 15U
Number of power modules 1 to 2 x 25 kW 1 to 4 x 25 kW
Configuration N, N+1 redundant
Power (Sn) 25 to 50 kVA 25 to 75 kVA
Power (Pn) 25 to 50 kW 25 to 75 kW
Input / output 3 / 3
Input
Voltage 400 V 3ph (340 V to 480 V)
Frequency 50 / 60 Hz ±10 %
Power factor / THDI > 0.99 / < 3 %
Output
Voltage 380 / 400 / 415 V ±1 % 3ph+N
Frequency 50 / 60 Hz ±0.1 %
Voltage distortion < 1 % (linear load), < 4 % (non-linear load according to lEC 62040-3)
Short-circuit current up to 3 x In
Overload 125 % for 10 minutes, 150 % for 1 minute
Crest factor 3:1
Hot-swap bypass
VoltageRated output voltage ±15 % (configurable from 10 % to 20 %)
Frequency 50 / 60 Hz ±2 % (configurable for GenSet compatibility)
Weight 7 kg 7.5 kg
Efficiency (TÜV SÜD verified)
Online double conversion mode up to 96.5 %
Environment
Ambient temperature0 °C to 40 °C (15 to 25 °C for maximum battery life)
Relative humidity 0 to 95 % without condensation 
Maximum altitude 1000 m without derating (3000 m max)
Acoustic level at 1 m < 53 dBA
UPS rack  
Dimensions W x D x H 442 mm x 920 mm x 9 U 442 mm x 920 mm x 15 U
Weight (empty cabinet) 36 kg 42 kg
Degree of protectionIP20
Hot-swap power module
Height 3U
Weight 34 kg
Type Hot plug-in / Hot-swappable
MTBF > 1 000 000 hours (calculated and verified)
Hot-swap battery rack
Type Acid leak-proof – Long Life batteries
Protection Independent protection for each battery string
Dimensions W x D x H 442 mm x 890 mm x 4 U
Weight (empty rack) 15 kg
Standards
Safety IEC/EN 62040-1      
EMC IEC/EN 62040-2 Class C2
Performance IEC/EN 62040-3    
Product certification CE
UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings

Commercial (Hotel, shopping centre, stadium, cinema, TV station, etc.), Government, Residential.