Delphys BC

Reliable, simple and ready-to-use power protection.Three/three phase UPS from 200 to 300 kVA

The solution for

• Server rooms
• Service sector
• Infrastructure
• Healthcare sector
• Light industrial applications
 

Advantages

A complete, cost-effective solution

• Online double conversion mode with an output power factor of 0.9 providing 12% more active power compare to UPS with a power factor of 0.8.
• Dual input mains allows you to manage independent power sources.
• Increased system availability placing two UPS in parallel for 1+1 redundancy
• Internal manual bypass for easy maintenance without power interruption (1+1 configuration).
• Multilanguage display.

Tailored to your environment

• Saves space with a reduced footprint and optimized cabinet size.
• Low noise level.
• Compact, lightweight and easy to install
• No neutral required on rectifier input.
• Two-wire battery connection (only +/-).
• Extended battery life and performance with exclusive EBS battery charging management for increased battery life.
 

Preventive maintenance on UPS systems

Improving the reliability and durability of your critical power equipment

Ask for a FREE site survey! We‘ll install the correct UPS power systems for your site. We’re here to help you.

If you looking for continuous power control? Whatever UPS Power System you may require, our engineers will design the whole solution.

Standard electrical features

• Dual input mains.
• Integrated maintenance bypass.
• Backfeed protection: detection circuit.
• EBS (Expert Battery System) for battery management.

Electrical options

• External battery cabinet.
• External temperature sensor.
• Additional battery chargers.
• Shared battery.
• Galvanic isolation transformer.
• Parallel kit.
• ACS synchronization system.

Standard communication features 

• 2 slots for communication options.

Communication options

• ADC interface (configurable voltage-free contacts).
• MODBUS TCP.
• MODBUS RTU.
• PROFIBUS.
• NET VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.

Remote monitoring service

• LINK-UPS, remote monitoring service that connects your UPS to your Critical Power specialist 24 / 7.

 

Technical data

 

Sn [kVA]200300
Pn [kW]180270
Parallel configurationup to 6 units
Input
Rated voltage400 V 3ph
Voltage tolerances240 V to 480 V(1)
Rated frequency 50/60 Hz ± 10%
Power factor / THDI0.99 / < 3%
Output
Rated voltage400 V
Voltage tolerance static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency50 / 60 Hz
Frequency tolerance± 2% (configurable from 1% to 8%) 
Crest factor3:1
Bypass
Rated voltagerated output voltage
Voltage tolerance± 15% (configurable from 10% to 20%)
Rated frequency50/60 Hz
Frequency tolerance± 2% (configurable for Genset compatibility)
Efficiency
Online mode @ 100 % of loadup to 94%
Environment
Operating ambient temperaturefrom 0 °C up to + 40(1) °C
(from 15 °C to 25 °C for maximum battery life)
Relative humidity0% – 95% without condensation
Maximum altitude1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746)< 68 dBA< 71 dBA
UPS cabinet  
Dimensions W x D x H700 x 800 x 1930 mm1000 x 950 x 1930 mm
Weight500 kg830 kg
Degree of protectionIP20
ColoursRAL 7012, silver grey frontal door
Standards
SafetyIEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
PerformanceIEC/EN 62040-2, AS 62040.2
EMCIEC/EN 62040-3, AS 62040.3
Product declarationCE, RCM (E2376)

(1) Conditions apply.

UPS Selector
Find your UPS from 600 VA to 120 kVA.  Choose the best UPS solution for the current and future protection of your business.

Applications

Industry

Industry

Process manufacturing, Water treatment facilities, Machinery, Control room.

Healthcare

Healthcare

Operating theatres, intensive care units, laboratories, patient data systems, patient wards, examination rooms, sterilization rooms

Asset 2

Data Centres and Telecom

HVAC cooling units, Server room, Security Systems & Control rooms, Radio/TV stations

Infrastructure_1

Infrastracture

Airports, Harbours, Tunnels, Highways

Asset 1

Buildings

Commercial (Hotel, shopping centre, stadium, cinema, TV station, etc.), Government, Residential.